video corpo

MPC35

MPC35

MPC35

Product catalog summary
Overview
The Modular Plant Chamber 35 (MPC35) is a portable, stand-alone facility designed for plant research, offering a controlled environment for plant culture and seedling germination. It features a 35 cubic meter chamber with open wire shelves equipped with LED lights, and an airflow system that circulates conditioned air through primary, secondary, and HEPA filters.

Specifications
  • Volume: 35 cubic meters
  • Shelf Surface: 32.5 square meters, stainless steel wire shelves
  • Lighting: LED T8 tube lights, 6500K, 1400 Lumen
  • Temperature Range: 18°C to 30°C, with 1°C hysteresis
  • Humidity Range: 30% to 90% relative humidity, with 10% hysteresis
  • Power Supply: 410 Volt, three-phase or 230 Volt single-phase, 50 Hertz

Technology
The chamber uses a Programmable Logic Controller (PLC) for precise control, featuring inverter-driven water chiller systems for cooling and heating, and a steam generator for humidity control. All air ducting is insulated to enhance system efficiency.

Configuration
The standard setup includes a walk-in laboratory for gowning and sample manipulation, with controlled access to the growth chamber and separate access to the utilities chamber. Configurations can be customized to meet user requirements.

Additional Information
For ongoing product improvements, specifications may change without notice. For more options, visit the Laboratory Infrastructure Solutions website at www.LIS-Labs.com.
See more

Catalog excerpts

MPC35-1

Modular Plant Chamber 35 Portable stand-alone plant chamber with built in utilities to support plant culture work and seedling germination in a contained controlled environment of 35 cubic meter. The Modular Plant chamber model MPC33 offers a portable stand-alone walk in facility for plant research. The Modular Plant Chamber houses an environmentally controlled chamber fitted with open wire shelves, each fitted with LED lights. Airflow pattern in the MPC35 is from bottom to top, with air discharged from chamber sides to a central return air system. Conditioned air recirculates via Primary, secondary and HEPA filtration in an on-board utilities chamber. User parameters can be set from an on-board display, or remotely via a secure web based portal. User adjustable settings: Temperature adjustment range: 18 degrees Celsius to 30 Degrees Celsius, with a hysteresis of I degree Celsius. Humidity adjustment range: 30% relative humidity to 90% relative humidity, with a hysteresis of 10%. Day night cycle: set points and duration, with light on/off control.

 Open the catalog to page 1
MPC35-2

Technical data General: Growth chamber volume: 35 cubic meter. Shelve surface: 32,5 square meter. Shelve type: Stainless steel wire shelves. Shelf configuration: Rows, to end-user requirements. Lights: LED T8 tube lights 6500K, 1400 Lumen. MPC placement conditions: Stand-alone containerized unit for placement on level surface with walk-in access. Ambient conditions: Minus 5 degreed Celsius to 35 degrees Celsius. Power supply: 410 Volt, three phase or 230 Volt single phase, 50 Hertz. Technology employed: Control: Programmable Logic controller with LIS developed close control programme. Cooling...

 Open the catalog to page 2
MPC35-3

Standard configuration consists of a walk-in laboratory for gowning and sample manipulation. The laboratory provides controlled access to the Growth Chamber. Separate access to the Utilities chamber enhances systems security. Configuration may be customized to end-user requirements. Schematic 1. Indicative general arrangement of the Modular Growth Chamber 35 configuration. Schematic 2: Indicative general arrangement of the Modular Growth Chamber 35 airflow patterns. For more information on available options contact us via our web site at www.LIS-Labs.com. In the interest of ongoing product improvement,...

 Open the catalog to page 3

All Laboratory Infrastructure Solutions catalogs and technical brochures

  1. Plant Chamber

    2  Pages

*Prices are pre-tax. They exclude delivery charges and customs duties and do not include additional charges for installation or activation options. Prices are indicative only and may vary by country, with changes to the cost of raw materials and exchange rates.