Overview: This document provides a step-by-step guideline for replacing the overheating probe in models TK3000, TK6000, and TK9000. The procedure involves disconnection, removal, and replacement of components to ensure proper functioning of the equipment.
Equipment Required: Tongs, 7 black clamps, screwdrivers, and a probe with a red connector (spare part).
Procedure:
  • Step 1: Disconnect the chiller from the power supply. Use a screwdriver to remove 16 screws as indicated.
  • Step 2: Disconnect the ground wire from the cover and remove the cover.
  • Step 3: Disconnect the red probe connector from the main board. Cut the black clamps inside the chiller that secure the probe’s wire.
  • Step 4: Cut all black clamps securing the probe’s wire and extract the wire from the circular passage.
  • Step 5: Cut the last black clamp near the condenser, extract the probe, and replace it.
  • Step 6: Insert the new probe cable through the circular passage, connect the new probe connector to the main board, and secure the probe’s cable with new black clamps. Reattach the chiller cover and secure it with the 16 screws. Ensure the ground wire is connected to the cover before closing.
Critical Information: Ensure all connections are secure and the ground wire is properly reconnected to prevent electrical hazards.
See more

Catalog excerpts

OVERHEATING PROBEREPLACEMENT-1

OVERHEATING PROBE REPLACEMENT

 Open the catalog to page 1
OVERHEATING PROBEREPLACEMENT-2

7 black clamps Screw-drivers Probe with red connector (spare part) www.tecoonline.com | www.tecous.com

 Open the catalog to page 2
OVERHEATING PROBEREPLACEMENT-3

Disconnect the chiller form power supply. Using the screw-driver, remove the screws indicated in the picture here below (n°16 screws).

 Open the catalog to page 3
OVERHEATING PROBEREPLACEMENT-4

Disconnect ground wire from the cover Remove the cover

 Open the catalog to page 4
OVERHEATING PROBEREPLACEMENT-5

Disconnect the RED probe connector from main board. Cut the black clamps inside the chiller that embrace the probe’s wire.

 Open the catalog to page 5
OVERHEATING PROBEREPLACEMENT-6

Proceed to cut all black clamps that embrace the probe’s wire. Extract the wire from circular passage.

 Open the catalog to page 6
OVERHEATING PROBEREPLACEMENT-7

- Cut the last black clamp that embrace the probe’s wire and copper pipe near condenser - Extract the probe and replace it

 Open the catalog to page 7
OVERHEATING PROBEREPLACEMENT-8

- Insert probe cable in circular passage - Connect new probe connector to main board - Take new seven black plastic clamps and pinch the probe’s cable with the other cables as it was at the beginning. - Place the chiller cover in its position and then place the sixteen screws to close the chiller. ATTENTION: remember to connect ground wire to the cover before closing the chiller.